60.0KVA Online UPS (3:3 Phase)

Apollo 60.0KVA Online UPS (3:3 Phase)

      SPECIAL FEATURES:

  • True on-line dual conversion design

  • Generator Compatible

  • All  Protections over/low-voltage, overcurrent, overload

  • Intelligent Battery Management, extended battery life

  • Intelligent Self diagnose function, all kinds of fault protection 

  • Modularized  design of subsystems

  • Bypass back feed protection, battery leakage protection

  • Parallel Redundancy design, increase the system reliability

  • Customizable wide input voltage range

  • Large size input LCD display on front panel



Apollo 60.0KVA Online UPS (3:3 Phase)

Model

3P60K

Capacity (VA/Watts)

60K / 48K

INPUT


Nominal voltage

380/400/415Vac, (3Ph+N+PE)

Operating voltage range

208~478Vac

Operating frequency range

40 ~ 70Hz

Power factor

≥0.99

Harmonic distortion (THD)

2%(100% nonlinear load)

Bypass voltage range

Max. Voltage: 220V +25% (optional +10%, +15%, +20%) 230V 20% (optional +10%, +15%) 

240V 15% (optional +10%), Min voltage: -45% (optional -20%, -30%), Frequency protection rage: ±10%

Generator input

Support

OUTPUT


Output voltage

380/400/415Vac, (3Ph+N+PE)

Voltage regulation

±1%

Power factor

0.8/0.9 (Customized)

Output frequency

1.Line Mode: ±1%/±2%/±4%/±5%/±10% of the rated frequency (optional)

2.Battery Mode: (50/60±0.2%)Hz

Crest factor 

3:1

Harmonic distortion (THDv)

≤2% with linear load

≤5% with non linear load

Efficiency

95%

BATTERY


Battery voltage 

Standard unit: ±216Vdc; Long run unit Optional voltage: ±192V\±204V\±216V\±228V\±240Vdc

Battery type

12V/38Ah (standard unit)

Charge Current (A)

(charge current can be set according to battery capacity installed)

18A (Max.)

SYSTEM FEATURES


Transfer time

Utility to Batter : 0ms; Utility to bypass: 0ms

Overload

Line Mode

Load ≤110%: last 60min, ≤125%: last 1min, ≥150% turn to bypass mode immediately

Bat. Mode

Load ≤110%: last 10min, ≤125%: last 1min, ≤150%: last 5S, ≥150% shut down UPS immediately

Short circuit

Hold Whole System

Overheat 

Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately 

Low battery voltage 

Alarm and Switch off

Self-diagnostics

Upon Power On and Software Control

EPO (optional)

Shut down UPS immediately

Battery 

Advanced Battery Management

Nose Suppression

Complies with EN62040-2

Audible & Visual 

Line Failure, Battery Low, Overload System Fault

Status LED & LCD display

Line Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault

Reading on the LCD display

Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage & Inner Temperature

Communication interface

RS232, RS485, Parallel, Intelligent slot, Relay card (optional), SNMP card (optional)

ENCIRONMENTAL


Operating temperature

0~40°C

Storage temperature

-25 ~ 55°C

Humidity range 

0 ~ 95%  (non ─ condensing)

Altitude

<1500m